The most common design of CT consists of a length of wire wrapped many times around a silicon steel ring passed over the circuit being measured. The CT's primary circuit therefore consists of a single 'turn' of conductor, with a secondary of many hundreds of turns.
The CT acts as a constant-current series device with an apparent power burden a fraction of that of the high voltage primary circuit. Hence the primary circuit is largely unaffected by the insertion of the CT.
Common secondaries are 1 or 5 amperes. For example, a 4000:5 CT would provide an output current of 5 amperes when the primary was passing 4000 amperes. The secondary winding can be single ratio or multi ratio, with five taps being common for multi ratio CTs.
Current transformers are used extensively for measuring current and monitoring the operation of the power grid. The CT is typically described by its current ratio from primary to secondary. Often, multiple CTs are installed as a "stack" for various uses (for example, protection devices and revenue metering may use separate CTs). Similarly potential transformers are used for measuring voltage and monitoring the operation of the power grid.
For IEC (BSEN) typically, the secondary connection points are labeled as 1S1, 1S2, 2S1, 2S2 and so on, or in the ANSI/IEEE standard areas, X1...X5, Y1...Y5, and so on. The multi ratio CTs are typically used for current matching in current differential protective relaying applications.
For a three-stacked CT application, the secondary winding connection points are typically labelled Xn, Yn, Zn.
Care must be taken that the secondary of a current transformer is not disconnected from its load while current is flowing in the primary, as the transformer secondary will attempt to continue driving current across the effectively infinite impedance. This will produce a high voltage across the open secondary (into the range of several kilovolts in some cases), which may cause arcing. The high voltage produced will compromise operator and equipment safety and permanently affect the accuracy of the transformer.
For the IEC standard, accuracy classes for various types of measurement are set out in BSEN /IEC 60044-1, class 0.1, 0.2s, 0.2, 0.5, 0.5s, 1 & 3. It will be seen that the class designation is an approximate measure of the accuracy, e.g., class 1 current transformers have ratio error within 1% of rated current class 0.5 within a ratio error of 0.5% etc. Phase difference is important when power measurements are involved, i.e. when using wattmeter's, kilowatt-hour meters, VAr meters and Power Factor meters.
Rating factor is a factor by which the nominal full load current of a CT can be multiplied to determine its absolute maximum measurable primary current. Conversely, the minimum primary current a CT can accurately measure is "light load," or 10% of the nominal current (there are, however, special CTs designed to measure accurately currents as small as 2% of the nominal current). The rating factor of a CT is largely dependent upon ambient temperature. Most CTs have rating factors for 35 degrees Celsius and 55 degrees Celsius. It is important to be mindful of ambient temperatures and resultant rating factors when CTs are installed inside pad-mounted transformers or poorly ventilated mechanical rooms. Recently, manufacturers have been moving towards lower nominal primary currents with greater rating factors. This is made possible by the development of more efficient ferrites and their corresponding hysteresis curves. This is a distinct advantage over previous CTs because it increases their range of accuracy, since the CTs are most accurate between their rated current and rating factor.
In power systems applications, many CT configurations bypass this limitation by either being custom designed to slip around the bushing of a high-voltage transformer or circuit breaker, which automatically centers the conductor inside the CT window, or by having the primary turn permanently fixed inside the CT housing and accessible only by means of external terminals.
Specially constructed wideband current transformers are also used (usually with an oscilloscope) to measure waveforms of high frequency or pulsed currents within pulsed power systems. One type of specially constructed wideband transformer provides a voltage output that is proportional to the measured current. Another type (called a Rogowski coil) requires an external integrator in order to provide a voltage output that is proportional to the measured current. Unlike CTs used for power circuitry, wideband CTs are rated in output volts per ampere of primary current.